ETCR5000 Power Quality Analyzer

It is a comprehensive test instrument carefully developed by our company and specially designed for field test of three phases, multi-functional and intelligent, concise man-machine operation.

ETCR5000 Power Quality Analyzer

ETCR5000 Power Quality Analyzer 07.jpg

Introduction:

ETCR5000 Power Quality Analyzer is a comprehensive test instrument carefully developed by our company and specially designed for field test of three phases, multi-functional and intelligent, concise man-machine operation. 

It is easy to use, large LCD screen display, high resolution, interface in both Chinese and English, shock-proof shell structure and so on. 

Can simultaneously measure the 4-channel current (ABC three phase and neutral wire cur-rent), 4-channel voltage (ABC three-phase voltage and neutral line voltage to ground), the peak value of current voltage, maximum/minimum value over a period, three-phase imbalance factor, short-time voltage flicker, transformer K factor, active power, reactive power, apparent power, power factor and displacement power factor, active power, reactive power, apparent power, total harmonic distortion and harmonic, etc; 

Display real-time waveform, harmonic ratio bar charts of current voltage; 

Dynamically capture instantaneous change of voltage current, monitoring starting current, monitoring the power parameters and generate the alarm list, generate the trend chart for a long time record test data.


Functions:

1.Waveform real-time display (4 channels voltage/4 channels current).

2.True RMS values of voltages and currents.

3. The DC components of voltages.

4.Peak current and voltage values.

5.Minimum and maximum half-cycle RMS current and voltage values.

6.Phasor diagram display.

7.Measurement of each harmonic up to order 50.

8.Bar charts show harmonic ratios of current and voltage of each phase.

9.Total harmonic distortion (THD).

10.Active, reactive, apparent power, by phase and cumulative.

11.Active, reactive, apparent energy, by phase and cumulative.

12.Transformer K factor.

13.Power factors (PF) and displacement factors (DPF or COSΦ).

14.Short-term voltage flicker (PST).

15.Three phase unbalance(current and voltage).


Specifications:

1.1. Base condition and working condition

Influence   factor

Test   item

Base   condition

Working condition

Environment   temperature

All parameters

(23±2)°C

-10°C~ 40°C

Relative   humidity

All parameters

40%~ 60%

<80%

Phase-to-neutral   voltage

All parameters

(100±1%)V

1.0V~ 1000V

Phase-to-phase   voltage

True RMS phase-to-phase voltage

(200±1%)V

1.0V~ 2000V

Current

True RMS current

(5±1%)A

10mA~ 1000A

Network   frequency

All parameters

50Hz±0.1Hz

40Hz~ 70Hz

Phase   shift

Active power and active energy

Cosφ=1

Cosφ: 0.2~ 1.0

Reactive power and reactive energy

Sinφ=1

Sinφ: 0.2~ 1.0

Harmonic

All parameters

<0.1%

0.0%~ 100%

Voltage   unbalance

All parameters

<10%

0.0%~ 100%

Working   voltage of device

All parameters

DC9.8V±0.1V

DC9.5V~ 10.5V

External   electric field, magnetic field

All parameters

Should be avoided

Test   position

Measured related current parameters

Tested wire at the center of clamp.


General specifications:

Power   supply

Rechargeable lithium-ion battery pack 9.6V,   backup charger.

Battery   indicator

Battery symbol shows dump energy. When the   voltage is too low, automatic shutdown after the 1 minute.

Power   consumption

Current consumption of normal test 490 mA,   continuous working for 8 hours.

Display   mode

LCD color screen,5.6 inches

Size of   clamp

008 small sharp current clamp: 7.5mm×13mm;

040 circle current clamp: 35mm×40mm;

068 circle current clamp: 68mm×68mm;

Instrument   dimensions

L×W×H: 240mm×170mm×68 mm.

Number   of channels

4U/4I.

Phase-to   phase voltage

1.0V~2000V.

Phase-to-neutral   voltage

1.0V~1000V.

Current

008 current clamp: 10mA~10.0A;

040 current clamp: 0.10A~100A;

068 current clamp: 1.0A~1000A;

Optional current transformer: instrument   input current 1mA~500mA.

Frequency

40Hz~70Hz.

Parameters   of electricity

W, VA, Var, PF, DPF, cosφ, tanφ.

Energy   parameters

Wh, Varh, Vah.

Harmonic

Order 0~50.

Total   harmonic distortion

Order 0~50, each phase.

Expert   mode

Yes.

Number   of Transient records

150 sets.

Voltage   flicker

Yes.

Starting   current mode

Yes, 100 seconds.

3   phases unbalance

Yes.

Record

300 days(simultaneous recording 20   parameters, record one point every 5 seconds).

Min/Max   recorded value

Measurement of max. and min. values over a   period of time.

Alarm

40 types of parameter selections, 12,800   sets alarm logs.

Peak

Yes.

Phasor   diagram display

Automatically.

Capacity   of snapshots

60.

Menu   language

English/Chinese.

Communication

USB.

Automatic   switching off

When an alarm campaign is initiated or a   search for transients, an inrush current capture, or a trend recording is   pending or in progress, the device is not automatic switching off.

In other test mode, 15 minutes without   keystrokes, automatic shutdown after prompt 1 minute.

Backlight   function

Yes, suitable for use at night and dark   place.

Weight

Host: 1.6kg (with battery).

008 small sharp current clamp: 170g×4;

040 circle current clamp: 190g×4;

068 circle current clamp: 510g×4;

Test wires and power adapter: 900g;

Total weight: about 10.5kg (with   packaging).

Length   of voltage test wire

3m.

Length   of current sensor wire

2m.

Working   environment

-10°C~40°C; below 80%Rh.

Storage   environment

-10°C~60°C; below 70%Rh.

Input   impedance

Input impedance of test voltage: 1MΩ.

Withstand   voltage

Withstand 3700V/50Hz sinusoidal AC voltage   for 1 minute between instrument wiring and shell.

Insulation

Between instrument wiring and shell ≥10MΩ.

Structure

Double insulation, with insulation   vibration-proof sheath.

Safely   rules

IEC 61010 1000V Cat III / 600V CAT IV,   IEC61010-031, IEC61326, Pollution degree: 2.