It is mainly used in the grid connection of two high-voltage lines or the nuclear phase of the ring network Wireless transmission technology, safe and reliable operation Automatic shutdown without operation for 1 consecutive hour Both the transmitter and receiver have built-in rechargeable lithium batteries, and a 5V charger is configured
TAG-8000 Wireless High Voltage Phase Tester
Introduction:
The Wireless High Voltage Phase Detector (hereinafter referred to as "instrument") is applied to the grid-connected or circuit-connected nuclear phases of two High Voltage circuits.
It can also be used for remote (remote) nuclear phase to determine whether the color of the phase sequence is consistent with the name of the phase sequence.
It is suitable for live operation of 0.22 ~ 220kV ac transmission line and secondary side live operation, with high voltage galvanometer function.
It adopts wireless transmission technology, safe and reliable operation, convenient use, and overcomes many disadvantages of wired nuclear phase instrument.
Meanwhile, it is configured with GPS module, two or more instruments can be used for remote nuclear phase after matching and upgrading.
Features:
Measurement range across voltage is 0.22kv ~ 220kV.
The maximum transmission line-of-sight of the transmitter and receiving mainframe is about 100 meters.
The distance of two GPS mainframe is 0.3km ~ 800km in remote nuclear phase.
Human voice prompts measurement results and operation steps.
The 3.2-inch color screen simultaneously displays the phase difference, frequency, vector diagram and iso-phase results of two lines, and displays the number of GPS satellites, GPS timing status and time and other information.
Automatic shutdown without operation for 1 hour continuously.
Charger and receiver mainframe are built-in rechargeable lithium batteries with 5V charger.
Mainframe built-in 18650 lithium battery, battery capacity of 2500mAH. The transmitter has a built-in 14430 lithium battery with a capacity of 450mAH.
Specifications:
Phase difference accuracy | Error ≤5° |
Frequency accuracy | ±0.1Hz |
Cross voltage measurement range | 0.22kV~220kV |
Maximum transmission line-of-sight | about 100 meters |
High voltage leakage current when measured | <10uA |
Transmitter power consumption | <0.1W |
Receiving mainframe working power | <0.3W |
Working environment | -35℃--- +45℃ humidity≤95%RH |
Complete machine weight | 3.6kg |
Instrument packaging size | length 56cm* width 26cm* height 13cm |