DR-C50 Three Phase Capacitance and Inductance Tester

DR-C50 capacitor and inductance tester is newly developed to measure single or three capacitors of a group of parallel capacitors without disconnecting the wire, and can also measure the inductance, resistance and current.

DR-C50 Three Phase Capacitance and Inductance Tester


Introduction:

Capacitors in the capacitor bank are all in parallel in the field, so the leads need to be removed when workers measure with a general capacitance meter, which is a heavy workload and easily to cause wiring errors.

Our DR-C50 capacitor and inductance tester is newly developed to measure single or three capacitors of a group of parallel capacitors without disconnecting the wire, and can also measure the inductance, resistance and current.

The wiring is convenient, the operation is simple, which reduces the workload of the maintenance personnel and greatly improve the testing efficiency of the site and provides security for the normal operation of the power grid.

Specifications:

No.

Item Name

DR-C50 Capacitance & Inductance Tester

1

Capacitance measurement

Capacitance range

0.01μF ~ 3,300μF

Capacity range

5 ~ 20,000kvar

Accuracy

±1.0%

Resolution

0.001μF

2

Current measurement

Measurement range

0~20A

Accuracy

±3.0%

Resolution

0.01A

3

Inductance measurement

Measurement range

Small inductance method: 1mH-5Mh; Large inductance method: 5Mh-50H

Inductive reactance measurement range

50mΩ~20KΩ

Accuracy

±3.0%

Resolution

0.01Mh

4

Resistance measurement

Measurement range

Small inductance method: 50mohm-1ohm;

Large inductance method: 1ohm-20Kohm

Accuracy

0.01ohm

5

Power supply

220V±10%, 50Hz

Rated output

2V/20V/500VA

6

Working environment

0 ~ +40℃,≤90%RH

7

Dimension

400mm*320mm*220mm

8

Weight

8kg

 

Working Principle:

This capacitance inductance tester adopts a bridge circuit structure, and the standard capacitor and the measured capacitor are used as the two arms of the bridge circuit. When measuring the capacitance value of a capacitor, the test voltage is applied to both the standard capacitor and the tested capacitor, and the sensor simultaneously collects the current signal flowing through the standard capacitor and the tested capacitor and processes it to obtain the capacitance value of the tested capacitor.

 

Features:

Do not need to disassemble the bus bar, auto test, high precision and good stability.

Automatically switch the measurement range, LCD display, menu operation, can store and print the data.

Based on the synchronous sampling technology of standard capacitors and tested capacitors, it is not affected by power supply voltage fluctuations;

In additional, the measurement process is fully automatic, avoiding errors caused by manual operation, so it has the characteristics of good stability, good repeatability, accuracy and reliability.

Categories
Hot Products
Contact Us